Technical Characteristics –
- Each bushing is tested for AC withstand and partial discharge prior to leaving the factory.
- The equipment bushing is a moulded epoxy insulated part with a connector interface in accordance with CENELEC EN 50181. The 400SFR-B bushing has a shank outside this standard, adapted to use in SF6 gas.
Specification and Design –
- The bolted type equipment bushing 400SFR-B meets the requirements of CENELEC EN 50180 and IEC 60137.
Equipment Bushing Type | Voltage Um (kV) | Current Ir (A) |
---|---|---|
400SFR-B 1250 A | 12 | 1250 |
K400SFR-B 1250 A | 24 | 1250 |
M400SFR-B 1250 A | 36 | 1250 |
Nexans Euromold fixings for Equipment Bushings are also available. Connect with us to know more.